Cornwall Power Equipment Co.

Division of 1618327 Ontario Inc.

Telephone No:  (613) 938-8816     Toll Free:  1-800-363-0086

Fax: (613)938-4802   or  E-Mail:  info@cpec.ca

 

SACE

 

Year     1968

Type    RM 10

 

Rated Voltage            10 kv               Insulated Level 12 kv

            Rated Current            630 A              Rated Frequency            50hz

 

                                    Operating Duty            0    03s                   CO   3mn       CO

Breaking Capacity                                               14.4                                                .

                                                                                                                                    KA

Making Capacity                                                 37                                                 .

 

 

                                    Operating Duty            0    3mn       CO   3mn       CO

Breaking Capacity            19.3            19.3                 14.4                 12                            .

                                                                                                                                    KA

Making Capacity             50          50                    37                  31                            .

 

At The Voltage Of            3         6                        10                    12                            .            KV

 

                                    Short Time Current For 3s   20 KA

                                                                Operating Time                    40ms

                                                                Make Time                       120ms

  

42-1/2" High

2-1/2" Wide

HOME | CONTACT US